SYSTEM SENSOR
Advanced Wall Mounting for Fire Detection Panel, Carbon Monoxide Detector
Advanced Wall Mounting for Fire Detection Panel, Carbon Monoxide Detector
No se pudo cargar la disponibilidad de retiro
ELECTRICAL ESPECIFICATIONS:
System Voltage
Nominal: 12/24 VDC
Min: 10 VDC
Max: 33 VDC
- Avg. Standby Current: 20 mA
- Max Alarm Current: 40 mA (75 mA test)
- Alarm Contact Ratings: 30 VDC @ 0.5 A
- Trouble Contact Ratings: 30 VDC @ 0.5 A
- Audible Signal (temp 4 tone): 85 dBA min. in alarm (at 10ft)
- Max. Start-up Capacitance: 20 uF
PHYSICAL SPECIFICATIONS
- Operating Temperature Range: 0° to 40°C (32° to 104°F)
- Operating Humidity Range: 22 – 90% %RH
- Length: 5.1?
- Width: 3.3?
- Height: 1.3?
- Weight: 7 oz
- Wire Gauge Acceptance: 14-22 AWG
This product is intended for use in ordinary indoor locations.
GENERAL DESCRIPTION:
• Listed to UL standard 2075
• Six-wire, system monitored
• Local sounder
• Low current draw
• Alarm relay, Form C
• Trouble relay, Form A
• Dual LED’s
• Test/Hush button
• SEMS wiring terminals
• Mount to single gang electrical box or surface mount to the wall
• Optional drywall anchors included
Compartir
Bajas existencias: quedan 2